Automatic Voltage Regulator AVR R120 for Leroy Somer Generator

Automatic Voltage Regulator AVR R120 for Leroy Somer Generator for sale at FridayParts, Buy aftermarket parts For OTHER BRAND excavators, wheel loaders, bulldozer, backhoe, skid steer loader and so on.

US$216.83
Availability: In stock
SKU
EL1903347-HP32134

    Automatic Voltage Regulator AVR R120 for Leroy Somer Generator

    The R120 is used on the following Leroy Somer Alternators:
    TAL040 B, TAL040 C, TAL040 C1, TAL040 D, TAL040 E, TAL040 F
    TAL042 A, TAL042 B, TAL042 C, TAL042 D, TAL042 E, TAL042 F, TAL042 G, TAL042 H
    TAL044 A, TAL044 B, TAL044 C, TAL044 D, TAL044 D1, TAL044 E, TAL044 H, TAL044 J, TAL044 K

    SAME EXACT AVR AS:
    Leroy Somer Voltage Regulator AEM230RE005
    Leroy Somer Voltage Regulator 4969966

    Specification:
    Sensing input:
    - Voltage: 277 VAC ± 10% for 1-phase,
    415 VAC line-to-line ± 10% for 3-phase,
    2-line sensing. The AVR senses the true
    average of the line-to-line waveform. Use
    the resistor (SMD) network for trouble-free
    sensing and control of sensed voltage/ regulation.
    Input power:
    - Voltage: 277 VAC rms ± 10%
    - Frequency: 50/60 Hz
    Output power:
    - Voltage: 95 VDC for 240 VAC Input
    - Current:
    4 A DC
    6 A for 30 sec. (when allowed by the field resistance)
    Operating temperature: -20ºC to +70ºC
    Storage temperature: -40ºC to +80ºC
    Voltage setting: min ± 10% of rated voltage.
    Stability setting: can be adjusted to obtain
    a correct transient response in steady state.
    Under frequency roll-off setting: available
    below 46 Hz for 50 Hz and below 56 Hz for 60 Hz.
    Voltage build-up: 2 Volts (L-N)
    Voltage regulation: ± 1% at the AVR
    terminals with a THC <5%.
    Thermal drift: ± 1% for 30ºC change in temperature.
    Response time: less than 50 ms.
    Closed loop response: typically 0.5 sec to recover 98% of the defined voltage for a field forcing ratio of 1:2.
    Sensing loss protection: the voltage
    should disappear when the sensing circuit is open.
    Overexcitation protection: 10 VDC to 85 VDC.
    Set point: 60 VDC
    Protection fuse: 4 A, 240 VAC.
    Potentiometer sealing: except for the
    V-trim potentiometer, all potentiometers are sealed.
    Frequency roll-off indicator: LED provided (UF).
    Sensing loss indicator: LED provided (SL).
    Overexcitation indicator: LED provided (OE).
    Protection on the devices: suitable R-C
    snubber to be provided for the device used
    to protect against voltage surges.
    Potting/Encapsulation details: the
    components on the AVR should be
    completely encapsulated with suitable PU
    resin compound to absorb transients/
    vibrations during operation.
    Alternator excitation details: (typical)
    - Full load:
    Excitation voltage: 40 to 50 V
    Excitation current: 2.5 to 4.0 A